13-3. Address Setup

In case that addresses of the indoor units will be determined prior to piping work after cabling work

(Manual setting from remote controller)

<Address setup procedure>

Set an indoor unit per a remote controller.

Turn on power supply.

1

Push

SET

+

+

buttons simultaneously

for 4 seconds or more.

2

(

Line address) Using the temperature setup

/

buttons, set

12

to the item code.

3

Using timer time

/

buttons, set the line address.

4

Push

SET

button. (OK when display goes on.)

5

(

Indoor unit address) Using the temperature setup

/

buttons, set

13

to the item code.

6

Using timer time

/

buttons, set 1 to the line address.

7

Push

SET

button. (OK when display goes on.)

8

(

Group address) Using the temperature setup

/

buttons, set

14

to the item code.

9

Using timer time

/

buttons, set

0000

to Individual,

0001

to Master unit, and

0002

to sub unit.

10

Push

SET

button. (OK when display goes on.)

11

Push

button.

Setup completes.
(The status returns to the usual stop status.)

(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)

Line address

1

Indoor unit address

1

Group address

1

For the above example, perform setting by connecting
singly the wired remote controller without remote
controller inter-unit cable.

Group address

Individual

: 0000

Master unit : 0001
Sub unit

: 0002

In case of group control

OUT

IN

OUT

IN

2
1
2

UNIT

SET

CL

UNIT No.

SET DATA

R.C.

No.

3, 6, 9

11

1

2, 5, 8

4, 7, 10

1 2 3 4 5 6 7 8 9 10 11

END

END

<Operation procedure>