NOTIFICATION

It is not an abnormal phenomenon that electro-noise may be heard while heating the coil.

4. Short intermittent operation preventive control

Q

The compressor may not stop for preventing the compressor for 3 to 10 minutes after start of the
operation even if Thermo-OFF signal has been received from the indoor. This phenomenon is not
abnormal. (Continuous operation time of the compressor differs according to the operating status.)

R

If the equipment is stopped from the remote controller, the operation does not continue.

5. High-voltage suppression TE control (Only for SM800)

Q

This control suppresses that voltage becomes abnormally higher during cooling operation.

R

Stop the compressor under condition of TE

67

°

C, and count 1 on the error count.

S

After 2 minutes 30 seconds passed, if TE < 67

°

C, the compressor restarts and the error count is

cleared when the operation continues for 10 minutes.

T

When TE

67

°

C is detected again within 10 minutes, 1 is added to the error count and restart is

repeated.

U

If the error counts 10 are recognized, it is determined as an error and restart is not performed. Error
code

P04

is displayed.

V

After restarting the compressor, continue controlling by using 70% to 90% of the control value of the
current release control for minimum 30 minutes.

6. Over-current preventive control

Q

This control function stops the compressor when over-current preventive circuit has detected an
abnormal current.

R

The compressor restarts with error count 1 after 2 minutes 30 seconds.

S

If the error counts 4 are recognized, it is determined as an error and restart is not performed. Error
code

H01

,

H02

or

P26

is displayed.

7. Current release value shift control

1) Object: SM800

Q

This control function prevents troubles of the electron parts such as G-Tr of inverter of compressor

drive system and troubles of the compressor during cooling operation.

R

This control function corrects the current release control value ( 1) in item 3 of 9-2-2 by TO sensor

value.

S

The value to be corrected is based upon the following control diagram and correction value table.

SM800

T

a

b

c

d

39

°

C 40

°

C 60

°

C 80

°

C 85

°

C

Corrected value

2) Object: SM560

The current release value of a single-phase model is se-
lected from the right table according to TO sensor value.

Current release value shift control

TO

45

TO

40

TO < 45

TO < 45

SM560

7.07

7.90

10.22

T+8
T+7
T+5
T+4
T+2
T+1

T

T-1

TO [

C]

I

1 x a%

I

1 x b%

I

1 x c%

I

1 x d%

As

I

1