Toshiba RAV-SM560BT-E User Manual

Page 76

Advertising
background image

76

[P12 error]/[11 error]

<Only for 4-way air discharge cassette type models (RAV-SM560UT-E/RAV-SM800UT-E)>

Correct connection of connector.

Replace indoor fan motor.

*

1

Are not coil windings between

(Red lead) and (White lead),

between

(White lead) and (Black lead), between

(Black lead) and (Red lead) opened or shorted?

For resistance, see the following values.

AIU-P401H/HR, P451, P501, P561, P631, P711, P801

Approx. 70 to 100

AIU-P1121H/HR, P1401, P1601 Approx. 35 to 50

Is not earthed between cabinet and 1, 3, 5 10M or more

*

2

Check resistance of fan motor position detection circuit.

Is not coil winding between (Yellow lead) and (Pink lead)

opened or shorted? Resistance: Approx. 5 to 20k

*

3

Check fan motor position detection signal.

Using a tester, measure the voltage between CN334 and of

indoor P.C. board (MCC-1402) under condition that CN333 and

CN334 are mounted and the power is turned on.

Rotate the fan slowly with hands,

and check the pin voltage

swings between 0 to 5V voltage.

Between and : 5V

Check indoor P.C. board

(MCC-1402).

Defect Replace

Remove connectors CN333 and

CN334 of indoor unit P.C. board

(MCC-1402).

Replace indoor fan motor.

Replace indoor fan motor.

Replace indoor fan motor.

YES

NO

NO

NO

NO

NO

YES

YES

YES

YES

Turn off the power.

Is resistance value of fan motor connector

CN333 at motor side of indoor P.C. board

(MCC-1402) correct? *2

Are not there connections errors or

disconnection on connectors CN333 and CN334

of indoor unit P.C. board (MCC-1402)?

Are resistance values between phases

at fan motor connector CN333 motor side of

indoor P.C. board (MCC-1402) correct? *1

Is signal output of indoor fan motor

position detection correct? *3

Does the fan rotate without trouble

when handling the fan with hands?

1

3

3

5

5

1

1

5

4

5

4

1

CN333

CN334

Advertising
This manual is related to the following products: