Toshiba RAV-SM560BT-E User Manual

Page 123

Advertising
background image

123

NO

NO

YES

YES

* Refer to Characteristics-2.

* Refer to Characteristics-1.

Check 4-way valve.

Check CDB P.C. board.
Defect

Replace

* For RAV-SM560AT-E,

check control P.C. board.

Check and replace
2-way valve, check
valve, or electron
expansion valve.

Check indoor main P.C. board
(MCC-1370A) and
sub P.C. board (MCC-1370B).
Defect

Replace

Replace TC sensor.

Is operation of

4-way valve normal?

Is 200V applied to

4-way valve coil terminal

in heating operation?

Is circuit cable normal?

Check CDB P.C. board.

Are characteristics

of TC sensor resistance

value normal?

Check and correct circuit.

Correct connection of connector.

Replace TA sensor.

NO

NO

NO

YES

YES

YES

YES

NO

YES

NO

YES

NO

Check indoor P.C. board
(MCC-1370A).
Defect

Replace

Is connection of TA sensor connector

(Indoor main P.C. board CN04) normal?

Are characteristics of

TA sensor resistance value normal?

* For RAV-SM560AT-E,

replace control P.C. board.

Is flow of refrigerant by

2-way valve, check valve,

or electron expansion

valve normal?

[08 error]

In cooling operation, if high pressure is abnormally raised, [08 error] may be displayed. In this case, remove
cause of pressure up and then check again referring to the item [21 error].

[0C error]