Calling of error history

<Contents>

The error contents in the past can be called.

<Procedure>

1

Push

+

buttons simultaneously for 4

seconds or more to call the service check mode.

Service Check goes on, the item code

01

is

displayed, and then the content of the latest alarm is
displayed. The number and error contents of the
indoor unit in which an error occurred are displayed.

2

In order to monitor another error history, push
the set temperature

/

buttons to

change the error history No. (Item code).

Item code

01

(Latest)

Item code

04

(Old)

NOTE : Four error histories are stored in memory.

3

Pushing

button returns the display to usual

display.

<Requirement>

Do not push

button, otherwise all the error histories of

the indoor unit are deleted.

UNIT

SET

CL

UNIT No.

SET DATA

R.C.

No.

3

2

1

1 2 3

<Operation procedure>

Returned to usual display

(Group control operation)

In a group control, operation of maximum 8 indoor units can be controlled by a remote controller.

The indoor unit connected with outdoor unit (Individual/Master of twin) controls room temperature according to
setting on the remote controller.

<System example>

(1) Display range on remote controller

The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to the
master unit is reflected on the remote controller.

(2) Address setup

Turn on power of the indoor unit to be controlled in a group within 3 minutes after setting of automatic
address.

If power of the indoor unit is not turned on within 3 minutes (completion of automatic address setting), the
system is rebooted and the automatic address setting will be judged again.

1) Connect 3 In/Out cables surely.

2) Check line address/indoor address/group address of the unit one by one.

3) The unit No. (line/indoor gout address) which have been set once keep the present status as a rule if the

unit No. is not duplicated with one of another unit.

OUT

IN

Remote controller

1-1

OUT

IN

2-1

Master

OUT

IN

3-1

OUT

IN

4-1

OUT

IN

7-1

Max. 8 units