Toshiba RAV-SM560BT-E User Manual

Page 43

Advertising
background image

– 43 –

No.

9

Item

Drain pump control

(For the duct, when
the drain-up kit
(sold separately) is
mounted)

Outline of specifications

1) In cooling operation (including Dry operation), the

drain pump is usually operated.

2) If the float switch operates while drain pump

operates, the compressor stops, the drain pump
continues the operation, and a check code is
output.

3) If the float switch operates while drain pump stops,

the compressor stops and the drain pump oper-
ates. If the float switch keeps operating for approx.
4 minutes, a check code is output.

Remarks

Check code [P10]

When heating operation stops, the indoor fan operates
with LOW mode for approx. 30 seconds.

10

11

After-heat elimina-
tion

All modes

• In group twin/triple operation, the swinging

positions can be set up collectively or individu-
ally.

3) When the unit stops or when a warning is output,

the flap automatically moves downward.

4) While the heating operation is ready, the flap

automatically moves upward.

1) Flap position setup

• When the flap position is changed, the position

moves necessarily to downward discharge
position once to return to the set position.

• The flap position can be set up in the following

operation range.

Flap control

(For 4-way air
discharge cassette
type only)

Warning :

A check code is displayed
on the remote controller,
and the indoor unit stops.
(Excluding [F08] and
[L31])

In cooling/dry operation

In heating/fan operation

• In group twin/triple operation, the flap positions

can be set up collectively or individually.

2) Swing setup

• The swinging position can be moved in the

following operation range.