14-4. Troubleshooting for Each Check Code

[1A error]

For RAV-SM560AT-E, CN300 changes to
CN301, and CN301 to CN300, respectively.

Are connections of CN301 and

CN300 of CDB correct?

Does the fan rotate without trouble

when handling the fan with hands under condition

of removing CN301 and CN300 from CDB?

The status that the resistance values

between leads below are 50 to 80

for 40W motor (ICF-140-43) and 25 to 55

for 60W motor (ICF-140-63-1) is normal.

Between (Red lead) and (White lead)

Between (White lead) and (Black lead)

Between (Black lead) and (Red lead)

of motor winding of connector (CN301)

The status that there is

5k to 20k resistance values between

(Yellow lead) and (Pink lead)

of motor position detection of connector

(CN300, CN302) is normal.

Normal fan motor

Defective fan motor

NOTE :
However, GND circuit error inside of the motor is rarely detected even if the above check is carried out.
When the circuit does not become normal even if P.C. board has been replaced, replace outdoor fan motor.

Objective P.C. board

Fan motor winding

Motor position detection

RAV-SM560AT-E

RAV-SM800AT-E

Control P.C. board

CN300

CN301

CDB P.C. board

CN301

CN300

1

2

2

3

3

1

1

4

(CDB error)

NO

NO

NO

YES

YES

YES

YES

CN301

CN300