Toshiba RAV-SM560BT-E User Manual

Page 122

Advertising
background image

122

[04 error]

Correct inter-unit cable.

Replace IPDU.

Replace IPDU.

* For RAV-SM560AT-E,

replace control P.C. board.

Does outdoor unit operate?

NO

NO

NO

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

YES

YES

Are 1, 2, 3 inter-unit

cables normal?

Are connections of

connectors normal?

Correct connection
of connector.

Is case thermo

(CN500) connected?

Does LED (D05) (Orange)

on indoor main P.C. board flash?

Correct connection
of connector.

Check CDB.
Defect

Replace

Is DC310 to 340V

applied between terminals

of electrolytic capacitor

of IPDU main circuit?

* For RAV-SM560AT-E,

replace control P.C. board.

* For RAV-SM560AT-E,

check case thermo.

Is DC310 to 340V

power supplied to CDB?

(CN03)

Does case thermo operate?

* For RAV-SM560AT-E,

replace control P.C. board.

Check/Correct charged
refrigerant amount.

* For RAV-SM560AT-E,

replace control P.C. board.

Check CDB.
Defect

Replace

Check main indoor main P.C. board
(MCC-1370A).
Defect

Replace

Advertising