Indoor unit outdoor unit – Toshiba RAV-SM560BT-E User Manual

Page 21

Advertising
background image

– 21 –

Indoor Unit/Outdoor Unit

RAV-SM800UT-E, RAV-SM800BT-E, RAV-SM800KRT-E/RAV-SM800AT-E

*

4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

Standard

Cooling Overload

Low load

Standard

Heating Overload

Low load

Pressure

(MPa)

(kg/cm

²

G)

Pd

Ps

Pd

Ps

3.3

0.9 33.4

8.8

3.7

1.1 37.8 11.4

1.0

0.8 10.0

7.9

2.5

0.6 25.8

6.3

3.4

1.1 34.7 11.5

2.0

0.2 20.3

2.3

Pipe surface temperature (

°

C)

Discharge

Suction

Indoor heat Outdoor heat

exchanger

exchanger

(TD)

(TS)

(TC)

(TE)

86

11

9

44

90

21

18

54

19

4

4

8

67

6

42

2

85

23

55

16

89

–16

34

–18

Compressor

revolutions per

second (rps)

*

64

52

27

65

31

90

Indoor

fan

HIGH

HIGH

LOW

HIGH

LOW

HIGH

Indoor/Outdoor

temp. conditions

(DB/WB) (

°

C)

Indoor Outdoor

27/19

35/–

32/24

43/–

18/15.5

–5/–

20/–

7/6

30.–

24/18

15/–

–20/

(70%)

Indoor unit

Outdoor unit

Outer diameter of refrigerant pipe

Gas side

Ø

A

Liquid side

Ø

B

15.9mm

9.5mm

TCJ

sensor

Air heat exchanger

Strainer

Strainer

TC sensor

Refrigerant pipe

at liquid side

Outer dia. ØB

Refrigerant pipe

at gas side

Outer dia. ØA

Packed valve
Outer dia. ØB

Packed valve
Outer dia. ØA

Max
50m

TS sensor

Accumulator

(1500cc)

TD sensor

TO sensor

TE

sensor

4-way valve

(STF-0213Z)

Ш25

Ч

L160

Rotary compressor

(DA220A2F-20L)

Heat exchangerØ8

1 row 30 stages

FP1.3 flat fin

Modulating (PMV)

(SKV-18D26)

Capillary

Ш3

Ч

Ш2

Ч

L530

Ш25

Ч

L210

Muffler

R410A 1.5 kg

Cooling

Heating

Ps

Pd

Advertising