107

RAV-SM800AT-E LED display when SW800 : Bit 1, 2, 3, 4 OFF

When multiple errors are detected, the latest error is displayed.

While LED displays

(go on), there is the main cause of error in control at CDB side and it stops abnormally.

While LED displays

(flash), there is the main cause of error in control at IPDU side and it stops abnormally.

For an error in case thermo operation, the communication is interrupted on the serial circuit. If continuing the
case thermo operation, serial sending to the indoor unit is interrupted and a serial communication error is
output.

Table A

CDB side

IPDU side

No.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Item

TE sensor error

TD sensor error

TS sensor error

TO sensor error

Discharge temp error

Out DC fan error

Communication error between IPDU
(Abnormal stop)

High-pressure release operation

EEPROM error

Communication error between IPDU
(No abnormal stop)

G-Tr short-circuit protection

Detection circuit error

Current sensor error

Phase missing detection

Comp lock error

Comp breakdown

Check code

B type

18

19

18

1B

1E

1A

1C

21

14

16

17

17

1D

1F

LED display

D800

D801

D802

D803

(Red)

(Yellow)

(Yellow)

(Yellow)

: Go on,

: Go off,

: Flash (5 Hz)