Error mode detected by indoor unit (1), Error mode detected by indoor unit (2) – Toshiba RAV-SM560BT-E User Manual

Page 119

Advertising
background image

119

Error mode detected by indoor unit (1)

Operation of diagnostic function

Block

display

[MODE] lamp
5Hz flash

Check

code

Cause of operation

Error in indoor fan system

Revolutions frequency error of
fan

Status of air

conditioner

All stop

Condition

Displayed when
error is detected

Judgment and measures

1. Check indoor fan motor connector

circuit (CN210).

2. Check indoor fan.

3. Check indoor P.C. board (Main P.C.

board).

Operation
continues

Operation
continues

All stop

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

1. Check indoor P.C. board

(EEPROM and peripheral circuits)
(Main P.C. board).

Error in indoor unit or other
positions

1. EEPROM access error

Outside error input

Detected by input voltage level
from outside devices

1. Check outside devices.

2. Check indoor P.C. board (Main P.C.

board).

Outside interlock input

Detected by input voltage level
from outside devices

Error mode detected by indoor unit (2)

Operation of diagnostic function

Check

code

Cause of operation

Serial return signal is not sent
from No. 1 indoor unit to
remote controller.

Miscabling of inter-unit cable
between remote controller
and indoor unit

Miss-setting of indoor unit No.
(Group address)

Status of air

conditioner

ON/OFF

Condition

Displayed when
error is detected

Judgment and measures

1. Indoor unit does not completely operate.

Check inter-unit cable.

Check indoor P.C. board. (Main/Sub P.C. boards)

Check remote controller.

2. In normal operation

Check setting of indoor unit No.
(SW01) (Sub P.C. board)

Check remote controller.

Advertising