Toshiba RAV-SM560BT-E User Manual

Page 73

Advertising
background image

– 73 –

[E10 error]/[CF error]
<Only for 4-way air discharge cassette type (RAV-SM560UT-E/RAV-SM800UT-E)>

[E18 error]/[97 error]

*

[99 error]

*

: When central controller [99] is displayed, there are other causes of trouble.

[E08, L03, L07, L08 error]/

*

[96 error] [99 error]

*

: When central controller [99] is displayed, there are other causes of trouble.

E08 : Duplicated indoor unit numbers

L03 : Two or more master units in a group control

L07 : One or more group addresses of [Individual] in a group control

L08 : Unset indoor group address (99)

If the above is detected when power has been turned on, the mode automatically enters in automatic ad-
dress setup mode. (Check code is not displayed.)

However, if the above is detected during automatic address setup mode, the check code may be displayed.

[L09 error]/[46 error]

Is inter-unit cable of A and B normal?

Is there no disconnection

or contact error of connector on harness

from terminal block of indoor unit?

Is group control operation?

Is power of all indoor units turned on?

Correct inter-unit cable of remote controller.

Correct connection of connector.
Check circuit cables.

Check power connection of indoor unit.
(Turn on power again.)

Check indoor P.C. board (MCC-1402).
Defect

Replace

Set capacity data of indoor unit.
(Setup item code (DN) = 11)

Check indoor P.C. board (MCC-1402).
Defect

Replace

Check indoor control P.C. board (MCC-1402).
Defect

Replace

NO

NO

YES

YES

YES

NO

NO

Is capacity of indoor unit unset?

YES

NO