14-3. Check Code Table

Error mode detected by indoor unit (1)

Operation of diagnostic function

Block

display

[MODE]
[TIMER] lamp
5Hz flash

Check

code

Cause of operation

The serial signal is not output
from outdoor unit to indoor unit.

Miscabling of inter-unit cables

Defective serial sending
circuit on outdoor P.C. board

Defective serial receiving
circuit on outdoor P.C. board

Compressor case thermo
operation

Status of air

conditioner

Operation
continues

Condition

Displayed when
error is detected

Judgment and measures

1. Outdoor unit does not completely

operate.

Inter-unit cable check, correction of
miscabling

Outdoor P.C. board check, P.C. board
cables check

Compressor case thermo check

2. In normal operation

When outdoor sending serial LED
(Green) flashes, the receiving serial
LED (Orange) also flashes. : Indoor
P.C. board (Main P.C. board) check

When the receiving serial LED
(Orange) does not flash: Outdoor P.C.
board check

[MODE] lamp
5Hz flash

*

Operation
continues
(According
to remote
controller of
indoor unit)

Operation
continues

Operation
continues

Operation
continues

Operation
continues

Operation
continues

Operation
continues

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

1. Communication line check, miscabling

check
Power supply check for central
controller (Central control remote
controller, etc.) and indoor unit

2. Communication check (XY terminal)

3. Indoor P.C. board check

4. Central controller check

(Communication P.C. board)

BUS communication circuit error

* BUS communication was

interrupted over the specified
time.

1. Check central control system network

address setting. (SW02)

2. Indoor P.C. board check

3. Central controller check

(Communication P.C. board)

Network address miss-setting

Addresses of central
controllers (Central control
remote controller, etc.) are
duplicated.

Error in 4-way valve system

Indoor heat exchanger
temperature rise after start of
cooling operation.

Indoor heat exchanger
temperature fall after start of
heating operation.

1. Check 4-way valve.

2. Check 2-way valve and non-return

valve.

3. Check indoor heat exchanger sensor

(TC).

4. Check indoor P.C. board (Main P.C.

board).

Error in other cycles

Indoor heat exchanger temp
(TC) does not vary after start
of cooling/heating operation.

1. Compressor case thermo operation

2. Coming-off of detection part of indoor

heat exchanger sensor

3. Check indoor heat exchanger sensor

(TC).

4. Check indoor P.C. board (Main P.C.

board).

1. Check indoor temp sensor (TA).

2. Check indoor P.C. board (Main P.C.

board).

Coming-off, disconnection or
short of indoor temp sensor
(TA)

1. Check indoor temp sensor (TC).

2. Check indoor P.C. board (Main P.C.

board).

Coming-off, disconnection or
short of indoor temp sensor
(TC)

1. Check indoor temp sensor (TCJ).

2. Check indoor P.C. board (Main P.C.
board).

Coming-off, disconnection or
short of indoor temp sensor
(TCJ)

*

: No display in the setting at shipment