DN

01

02

03

06

0F

10

11

12

13

14

19

1E

28

2A

2b

2E

30

31

32

40

5d

60

8b

Item

Filter sign lighting
time

Dirty state of filter

Central control
address

Heating suction temp
shift

Cooling only

Type

Indoor unit capacity

Line address

Indoor unit address

Group address

Flap type
(Adjustment of air
direction)

Temp difference of
automatic cooling/
heating mode
selection COOL

HEAT, HEAT

COOL

Automatic reset of
power failure

Option

Thermo output
selection (T10

ƒ

)

Option

Option

Option

Sensor selection

Option

High ceiling selection
(Air volume selection)

Timer set
(Wired remote
controller)

Correction of high
heat feeling

Description

0000 : None

0001 : 150H

0002 : 2500H

0003 : 5000H

0004 : 10000H

0005 : Clogged sensor used

0000 : Standard

0001 : High degree of dirt

(Half of standard time)

0001 : No.1 unit

to

0064 : No.64 unit

0099 : Unfixed

0000 : No shift

0001 : +1

°

C

0002 : +2

°

C

to

0010 : -10

°

C

(Up to recommendation + 6)

0000 : Heat pump

0001 : Cooling only

(No display of [AUTO] [HEAT])

0000 : (Air discharge cassette 1) 0001 : (Air discharge cassette 4) to 0037

0000 : Unfixed

0001 to 0034

0001 : No.1 unit

to

0030 : No.30 unit

0001 : No.1 unit

to

0064 : No.64 unit

0000 : Individual

0001 : Master of group

0002 : Sub of group

0000 : No flap

0001 : Swing only

0004 : 4-way

0000 : 0 deg

to

0010 : 10 deg

(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)

0000 : None

0001 : Reset

0000 : Indoor thermo ON

0001 : Output of outdoor comp-ON

receiving

0000 : Body TA sensor

0001 : Remote controller sensor

0000 : Standard filter
0001 : Oil guard, Super-long life, Optical regenerative deodorization
0003 : High performance (65%), High performance (90%),

High antibacterial performance (65%)

0000 : Available (Operable)

0001 : Unavailable (Operation prohibited)

0000 : None

0001 : Correction

At shipment

According to type

0000 : Standard

0099 : Unfixed

0002 : +2

°

C

(Floor type 0000: 0

°

C)

0000 : Shared for cooling/

heating

According to model type

According to capacity type

0099 : Unfixed

0099 : Unfixed

0099 : Unfixed

According to type

0003 : 3 deg

(Ts±1.5)

0000 : None

0002 : Default

0000: Thermo. ON

0000 : Default

0000 : Default

0000 : Default

0000 : Body sensor

0003 : Default

0000 : Standard

0000 : Available

0000 : None