Toshiba RAV-SM560BT-E User Manual

Page 62

Advertising
background image

62

2. Outdoor fan control (Object: SM560)

The outdoor fan is controlled by TO sensor and the revolutions frequency of the compressor (rps).
The outdoor fan is controlled by every 1 tap of DC fan control (8 taps). According to each operation mode,
the fan is operated by selecting an outdoor fan operation tap in the following table based upon the conditions
of TO sensor and the compressor operation (rps).

Allocations of fan tap revolutions

Tap

SM560

Revolutions per
minute (rpm)

F1

F2

F3

F4

F5

F6

F7

F8

960

870

870

870

750

700

540

390

In cooling operation

In heating operation

3. Coil heating control

1) This control function heats the compressor by turning on the stopped compressor instead of a case

heater. It purposes to prevent slackness of the refrigerant inside of the compressor.

2) As usual, turn on power of the compressor for the specified time before a test run after installation,

otherwise a trouble of the compressor may be caused. As same as a test run, it is recommended to turn
on power of the compressor beforehand when starting operation after power of the compressor has been
interrupted for a long time.

3) A judgment for electricity is performed by TD and TO sensors. If TO sensor is defective, a backup control

is automatically performed by TE sensor. For a case of defective TO sensor, judge it with the outdoor LED
display.

4) Coil heating is controlled by TD and TE sensor.

5) For every model, the power is turned off when TD is 30

°

C or more.

Frequency of the

compressor (rps)

TO

38

°

C

TO < 38

°

C

To 14

To 14

35 to MAX

F7

F4

F3

F7

F5

F4

Frequency of the

compressor (rps)

TO

5.5

°

C

TO < 5.5

°

C

To 14

To 14

35 to MAX

F7

F6

F4

F6

F6

F3

L

M

SM800

20W and equivalent

40W and equivalent

L

M

H

SM560

10W and equivalent

20W and equivalent

30W and equivalent

* TD sensor is read in once per 15 minutes

.

No power-ON

Continuous ON (L)

Continuous ON (M)

No power-ON

Continuous ON (L)

Continuous ON (M)

Continuous ON (H)

No power-ON

Continuous ON (L)

Continuous ON (M)

Power-ON condition
TD < 30

C

(In trouble of sensor)

(Object: SM560)

TO [

C]

TO [

C]

TO [

C]

20
18
12
10

18
15
10

8

10

9
4
3
2
1

Advertising
This manual is related to the following products: