10-2. Check Code List

Error mode detected by indoor unit

: Flash,

: Go on,

: Go off

Wireless sensor

lamp display

Operation Timer

Ready

Wired remote

controller

Check code

E03

E04

E08

L03

L07

L08

L09

L30

P01

P10

P12

P19

P31

F01

F02

F10

F29

E10

E18

Diagnostic function

Cause of operation

No communication from remote controller (including wireless)
and communication adapters

The serial signal is not output from outdoor unit to indoor unit.

Miscabling of inter-unit cables

Defective serial sensing circuit on outdoor P.C. board

Defective serial receiving circuit on indoor P.C. board

Duplicated indoor unit addresses

Duplicated indoor master units

There is group line in individual indoor units.

Unsetting of indoor group address

Unset indoor capacity

Abnormal outside interlock input

Fan motor thermal protection

Float switch operation

Disconnection, coming-off, defective float switch contactor
of float circuit

Indoor DC fan error

Error in 4-way valve system

Indoor heat exchanger temperature lowered after start of
heating operation.

Own unit stops while warning is output to other indoor units.

Coming-off, disconnection or short of indoor heat exchanger
sensor (TCJ)

Coming-off, disconnection or short of indoor heat exchanger
sensor (TC)

Coming-off, disconnection or short of indoor heat exchanger
sensor (TA)

Indoor EEPROM error

EEPROM access error

Communication error between indoor MCU

Communication error between fan driving MCU and main
MCU

Regular communication error between master and sub indoor
units or between main and sub indoor units

Status of air

conditioner

Stop
(Automatic reset)

S top
(Automatic reset)

Stop

Stop

Stop

Stop

Stop

Stop

Stop
(Automatic reset)

Stop (Sub unit)
(Automatic reset)

Stop
(Automatic reset)

Stop
(Automatic reset)

Stop
(Automatic reset)

Stop
(Automatic reset)

Stop
(Automatic reset)

Stop
(Automatic reset)

Condition

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Judgment and measures

1. Check cables of remote controller and communication adapters.

Handy remote controller LCD display OFF (Disconnection)

Central remote controller [97] check code

1. Outdoor unit does not completely operate.

Inter-unit cable check, correction of miscabling, case thermo operation

Outdoor P.C. board check, P.C. board cables check

2. In normal operation

P.C. board (Indoor receiving/Outdoor sending) check

1. Check whether there is modification of remote controller connection (Group/

Individual) or not after power has been turned on (finish of group configuration/
address check).

* If group configuration and address are not normal when the power has been turned

on, the mode automatically shifts to address setup mode. (Resetting of address)

1. Set the indoor capacity. (DN=I1)

1. Check outside devices.
2. Check indoor P.C. board.

1. Check thermal relay of fan motor.
2. Check indoor P.C. board.

1. Defect of drain pump
2. Clogging of drain pump
3. Check float switch.
4. Check indoor P.C. board.

1. Defective detection of position
2. Over-current protective circuit of indoor fan driving unit operates.
3. Lock of indoor fan
4. Check indoor P.C. board.

1. Check 4-way valve.
2. Check indoor heat exchanger (TC/TCJ) sensor.
3. Check indoor P.C. board.

1. Judge sub unit while master unit is in [E03], [L03], [L07], [L08].
2. Check indoor P.C. board.

1. Check indoor heat exchanger temperature sensor (TCJ).
2. Check indoor P.C. board.

1. Check indoor heat exchanger temperature sensor (TC).
2. Check indoor P.C. board.

1. Check indoor heat exchanger temperature sensor (TA).
2. Check indoor P.C. board.

1. Check indoor EEPROM. (including socket insertion)
2. Check indoor P.C. board.

1. Check cables of remote controller.
2. Check power cables of indoor unit.
3. Check indoor P.C. board.

1. Check cables of remote controller.
2. Check indoor power cable.
3. Check indoor P.C. board.