3-3. Tools

3-3-1. Required Tools

The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is

changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing

dimensions and opposite side dimension of flare nut (For

1/2 in. 12.7mm) copper pipe) of the refrigerant

piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,

clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.

Tools exclusive for R410A (The following tools for R410A are required.)

Tools whose specifications are changed for R410A and their interchangeability

No.

1

2

3

4
5
6

7

8
9

10

Used tool

Flare tool
Copper pipe gauge for

adjusting projection

margin
Torque wrench

[(For Ø1/2 (12.7mm)]
Gauge manifold
Charge hose
Vacuum pump adapter
Electronic balance for

refrigerant charging
Refrigerant cylinder
Leakage detector
Charging cylinder

Usage

Pipe flaring

Flaring by

conventional flare tool

Connection of flare nut

Evacuating, refrigerant

charge, run check, etc.

Vacuum evacuating

Refrigerant charge

Refrigerant charge
Gas leakage check
Refrigerant charge

R410A

air-water heat pump installation

Existence of

new equipment

for R410A

Yes

Yes

Yes

Yes

Yes

Yes

Yes
Yes

(Note 2)

Whether conven-

tional equipment

can be used

*

(Note 1)

*

(Note 1)

Ч
Ч
Ч

Ч

Ч

Ч

Ч

Conventional air-water

heat pump installation

Whether new equipment

can be used with

conventional refrigerant

¡

*

(Note 1)

Ч
Ч

¡
¡

Ч

¡

Ч

(Note 1)

When flaring is carried out for R410A using the conventional flare tools, adjustment of projection

margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.

(Note 2)

Charging cylinder for R410A is being currently developed.

General tools (Conventional tools can be used.)

In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary

as the general tools.

1. Vacuum pump

Use vacuum pump by attaching

vacuum pump adapter.

2. Torque wrench [For Ш1/4, Ш3/8 in.

(∅

6.35,

9.52mm)]

4. Reamer
5. Pipe bender
6. Level vial
7. Screwdriver (+, –)
8. Spanner or Monkey wrench

9. Hole core drill [Ø2-9/16 in. (65mm)]

10. Hexagon wrench

[Opposite side 3/16 in. (4mm)]

11. Tape measure

12. Metal saw

Also prepare the following equipments for other installation method and run check.

1. Clamp meter
2. Thermometer

3. Insulation resistance tester
4. Electroscope

3. Pipe cutter

FILE NO. SVM-10019