Toshiba RAS-09LKV-UL User Manual

Page 33

Advertising
background image

– 33 –

Item

4. Capacity

control

Operation flow and applicable data, etc.

The cooling or heating capacity depending on the load is

adjusted.
According to difference between the setup value of tempera-

ture and the room temperature, the capacity is adjusted by

the compressor revolution.

Description

1) The difference between set

temperature on remote controller

(Ts) and room temperature (Ta)

is calculated.

2) According to the temperature

difference, the correction value of

Hz signal which determines the

compressor speed is set up.

3) The rotating position and speed

of the motor are detected by the

electromotive force occurred on

the motor winding with operation

of the compressor.

4) According to the difference

resulted from comparison of the

correction value of Hz signal with

the present operation Hz, the

inverter output and the commuta-

tion timing are varied.

5) Change the compressor motor

speed by outputting power to the

compressor.
* The contents of control

operation are same in cooling

operation and heating

operation

This function prevents troubles on the electronic parts of the

compressor driving inverter.
This function also controls drive circuit of the compressor

speed so that electric power of the compressor drive circuit

does not exceed the specified value.

5. Current release

control

Outdoor temp. To

Setup of current release point

Outdoor unit inverter main

circuit control current

High

Low

Reduce compressor speed

Operating current ≤

Setup value

1) The input current of the outdoor

unit is detected in the inverter

section of the outdoor unit.

2) According to the detected

outdoor temperature, the

specified value of the current is

selected.

3) Whether the current value

exceeds the specified value or

not is judged.

4) If the current value exceeds the

specified value, this function

reduces the compressor speed

and controls speed up to the

closest one commanded from the

indoor unit within the range

which does not exceed the

specified value.

Outdoor temp.

Cooling current release value

Heating current release value

RAS-09LAV-UL RAS-12LAV-UL RAS-09LAV-UL RAS-12LAV-UL

113ºF (45ºC)

104ºF (40ºC)

61ºF (16ºC)

52ºF (11ºC)

111ºF (44ºC)

102ºF (39ºC)

60ºF (15.5ºC)

51ºF (10.5ºC)

3.97A

4.35A

6.30A

4.27A

4.88A

8.47A

6.30A

7.72A

6.30A

8.10A

6.30A

8.47A

FILE NO. SVM-10019

Set temp. (Ts)

Room temp. (Ta)

Correction value of Hz signal

Detection of electromotive force

of compressor motor winding

Inverter output change

Commutation timing change

Change of compressor speed

Remote contr oller

Indoor unit

Ts

−Ta

Correction value of Hz signal- Operating Hz

Detection of motor speed (Operation Hz)

and rotor position

Capacity control continues

Current decrease