7-2. Operation Data

<Cooling>

Tempeature

Model name

Standard

Heat exchanger

Indoor

Outdoor

Compressor

condition(°C)

RAS-

pressure

pipe temp.

fan mode

fan mode

revolution

Indoor

Outdoor

P Psia (MPa)

T1 °F (°C)

T2 °F (°C)

(rps)

80/67

98/75

137 to 160

54 to 57

99 to 102

(26.7/19.4)

(35/23.9)

(0.9 to 1.1)

(12 to 14)

(37 to 39)

116 to 145

52 to 55

104 to 107

(0.8 to 1.0)

(11 to 13)

(42 to 44)

<Heating>

Tempeature

Model name

Standard

Heat exchanger

Indoor

Outdoor

Compressor

condition(°C)

RAS-

pressure

pipe temp.

fan mode

fan mode

revolution

Indoor

Outdoor

P Psia (MPa)

T1 °F (°C)

T2 °F (°C)

(rps)

70/60

47/43

363 to 392

102 to 105

32 to 37

(21.1/15.6)

(8.3/6.1)

(2.5 to 2.7)

(39 to 41)

(0 to 3)

377 to 406

106 to 106

32 to 36

(2.6 to 2.8)

(41 to 43)

(0 to 2)

NOTES :

1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.

(Thermistor themometer)

2. Connecting piping condition : 16 ft (5m)

62

High

High

64

09LKV-UL

12LKV-UL

High

High

12LKV-UL

High

High

77

High High 60

09LKV-UL

FILE NO. SVM-10019

– 23 –