2. operation data – Toshiba RAS-09LKV-UL User Manual
Page 23

7-2. Operation Data
<Cooling>
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
RAS-
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P Psia (MPa)
T1 °F (°C)
T2 °F (°C)
(rps)
80/67
98/75
137 to 160
54 to 57
99 to 102
(26.7/19.4)
(35/23.9)
(0.9 to 1.1)
(12 to 14)
(37 to 39)
116 to 145
52 to 55
104 to 107
(0.8 to 1.0)
(11 to 13)
(42 to 44)
<Heating>
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
RAS-
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P Psia (MPa)
T1 °F (°C)
T2 °F (°C)
(rps)
70/60
47/43
363 to 392
102 to 105
32 to 37
(21.1/15.6)
(8.3/6.1)
(2.5 to 2.7)
(39 to 41)
(0 to 3)
377 to 406
106 to 106
32 to 36
(2.6 to 2.8)
(41 to 43)
(0 to 2)
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 16 ft (5m)
62
High
High
64
09LKV-UL
12LKV-UL
High
High
12LKV-UL
High
High
77
High High 60
09LKV-UL
FILE NO. SVM-10019
– 23 –