Toshiba RAS-09LKV-UL User Manual

Page 37

Advertising
background image

– 37 –

Item

9. ECO

operation

Operation flow and applicable data, etc.

When pressing [ECO] button on the remote controller, a
Economic operation is performed.

<Cooling operation>

This function operates the air conditioner with the difference
between the set and the room temperature as shown in the
following figure.

Description

<Heating operation>

1) The difference of room temperature

and set temperature are separated
in to A zone, B zone and C zone.

Three zone will changed again 30

minutes after ECO operation start.

* 12 (DRY max - COOL min) /6 x 5 + COOL min

* 11 (DRY max - COOL min) /6 x 4 + COOL min

* 10 (DRY max - COOL min) /6 x 3 + COOL min

* 9 (DRY max - COOL min) /6 x 2 + COOL min

* 8 (DRY max - COOL min) /6 x 1 + COOL min

(Room temp.

– Set temp.)














(3.5)
(3.0)
(2.5)

(1.5)
(1.0)

TSC

(-1.0)

(-2.0)

(5.5)

1H

2H

11

10

7

6

5

4
3

2

1

OFF

Dry Max

*12
*11

*9

*8

*10

0.0

(6.0)

(6.5)

3H

4H

(5.0)

(4.5)

(4.0)

(2.0)

(0.5)

(-0.5)

12

9

8

Time

Zone Frequency

Min
Hz

The indoor fan speed is not controlled and can be selected


Hz 09LKV-UL 12LKV-UL

Cool min

DRY max

20

35

11

31

1) The control target temperature

increase 1.0°F (0.5ºC) per hour
up to 3.5°F (2°C) starting from the

set temperature when ECONO

2) The indoor fan speed is depend

on presetting and can change
every speed after setting ECO

operation.

<Cooling operation>

2) The compressor speed is

controlled as shown on the table.

3) The compressor speed is

controlled as shown in the left
figure.

6.3
5.5
4.5

2.7
2.0

-2.0

-3.5

10.0

11.0

11.7

9.0
8.0
7.0

3.5

1.0

-1.0

(°C)

°F

FILE NO. SVM-10019

has been received.

during the ECO operation.

3) The indoor fan speed is not

controlled and can be selected
during the ECO operation.

< Heating Operation >

ECO Start

30 minutes

Time

Compressor speed (Hz)

Ro

o

m

te

mp

. - S

et te

mp

.

Zone

09LKV-UL

12LKV-UL

Model

0.0

(0.0)

Compressor stop

-2.0

-3.5

-5.5

-7.0

o

F

(

o

C)

(1.0)

(2.0)

(3.0)

(4.0)

B

A

(7.0)

(8.0)

(11.0)

-20.0

-22.0

(5.0)

(6.0)

(12.0)

Linear aproximation

between A to C

50

43

-16.0

-18.0

20

13

(9.0)

(10.0)

C

-12.5

-14.0

-9.0

-11.0

A Zone

B Zone

C Zone

A Zone

B Zone

C Zone