Item

6. Release protective

control by tempera-
ture of indoor heat
exchanger

Operation flow and applicable data, etc.

<In cooling/dry operation>

(Prevent-freezing control for indoor heat exchanger)
In cooling/dry operation, the sensor of indoor heat

exchanger detects evaporation temperature and

controls the compressor speed so that temperature of

the heat exchanger does not exceed the specified

value.

Description

1) When temperature of the indoor

heat exchanger drops below 41°F

(5°C), the compressor speed is

reduced. (P zone)

2) When temperature of the indoor

heat exchanger rises in the

range from 43°F (6°C) to under

45°F (7°C), the compressor

speed is kept. (Q zone)

3) When temperature of the indoor

heat exchanger rises to 45°F (7°C)

or higher, the capacity control

operation returns to the usual

control in cooling operation.

(R zone)

1) When temperature of the indoor

heat exchanger rises in the

range from 126°F (52°C) to 131°F

(55°C), compressor speed is kept.

(Q zone)
When temperature of the indoor

heat exchanger drops in the

range from 118°F (48°C) to under

131°F (55°C) the compressor

speed is kept. (Q zone)

2) When temperature of the indoor

heat exchanger rises to 131°F

(55°C) or higher, the compressor

speed is reduced. (P zone)

3) When temperature of the indoor

heat exchanger does not rise to

126°F (52°C), or when it drops

below to 118°F (48°C), the capacity

control operation returns to the

usual control in heating operation.

(R zone)

<In heating operation>

(Prevent-overpressure control for refrigerating cycle)
In heating operation, the sensor of indoor heat ex-

changer detects condensation temperature and controls

the compressor speed so that temperature of the heat

exchanger does not exceed the specified value.

(7 C)

(6 C)

(5 C)

R

Q

P

(55 C)

(52 C)

(48 C)

P

Q

R

Usual cooling capacity control

Reduction of compressor speed

Indoor heat e

xchanger temper

ature

When the value is

in Q zone, the

compressor speed

is kept.

Reduction of compressor speed

Usual heating capacity control

Indoor heat e

xchanger temper

ature

When the value is

in Q zone, the

compressor speed

is kept.

45 F

43 F

41 F

131 F

126 F

118 F

FILE NO. SVM-10019