Toshiba RAS-09LKV-UL User Manual

Page 31

Advertising
background image

– 31 –

Item

2. Indoor fan

motor control

Operation flow and applicable data, etc.

<In heating operation>

Description

1) When setting the fan speed to L,

L+, M, M+ or H on the remote

controller, the operation is per-

formed with the constant speed

shown in Fig. 3 and Table 1.

2) When setting the fan speed to

AUTO on the remote controller,

revolution of the fan motor is

controlled to the fan speed level

shown in Fig. 5 according to the set

temperature and room temperature.

3) Min air flow rate is controlled by

temperature of the indoor heat

exchanger (Tc) as shown in Fig. 4
for prevent high temperature of heat

exchanger.

4) Cold draft prevention, the fan speed

is controlled by temperature of the

[In starting and in stability]

(Fig. 3)

(Fig. 4)

(Fig. 5)

Cold draft preventive control

(Fig. 6)

L
L+
M
M+
H

W8

(L + M) / 2

WA

(M + H) / 2

WE

Indication

Fan speed

Fan speed setup

HEAT ON

AUTO

YES

NO

MANUAL

TC ≥ 107.6ºF (42 C)

Min air flow rate control

Tc ºF (ºC)

Limited to Min WD tap

* Fan speed =

(TC –

– W8) + W8

No limit

*

Fan speed

AUTO

Basic fan control

* No limitation while fan speed MANUAL mode is in stability.
* A: When Tsc

≥ 75°F (24°C), A is 75°F (24°C), and

Tsc: Set value

b

c

d

e

f

g

L+ (W9)

M+ (WD)

*1

*2

*3

H (WE)

H (WE)

Linear-approximate
H and SUL with Tc.

SUL (W2)

Stop

115 (46) 115 (46)

Tc

93 (34)

*A+4

*A+4

*A+4

*A-4

*A-4

*A-4

Fan speed MANUAL in starting
Fan speed AUTO in stability
Fan speed AUTO in starting

*1: Fan speed = [(M+)

− (L+)] x 1 4 + L+

*2: Fan speed = [(M+)

− (L+)] x 2 4 + L+

*3: Fan speed = [(M+)

− (L+)] x 3 4 + L+

(Calculated with linear approximation from M+ and L+)

Ta °F [°C]

TSC

-1.0 (-0.5)

-2.0 (-1.0)

-2.7 (-1.5)

-3.5 (-2.0)

-4.5 (-2.5)

-9.0 (-5.0)

-10.0 (-5.5)

°F (°C)

113 (45) 113 (45) 91 (33)

91 (33) 91 (33)

70 (21)

90 (32) 90 (32)

68 (20)

when Tsc < 75°F (24°C), A is Tsc

FAN AUTO

FAN Manual

In starting

• Until 12 minutes passed after operation start

• When 12 to 25 minutes passed after operation

start and room temp. is 5.4°F (3°C) or lower than set temp.

• Room temp. < Set temp. -7°F (– 4°C)

In stability

• When 12 to 25 minutes passed after operation start

and room temp. is higher than [set temp. -5.4ºF (–3°C)]

• When 25 minutes or more passed after operation start
• Room temp.

Set temp. -6.3°F (–3.5°C)

5) In order to prevent Cold draft when

compressor stop during heating

operation. Then louver will move to

upper position and fan speed will

reduce or off.

FILE NO. SVM-10019

126 (52)

124 (51)

108 (42)

106 (41)

indoor heat exchanger (Tc) as shown

in Fig. 6 for keep warm temperature

of air flow.