– 22 –

RAS-12LKV-UL / RAS-12LAV-UL

NOTE :
• The maximum pipe length of this air conditioner is 66ft (15 m). When the pipe length exceeds 50ft (15m), the additional

Max. : 66ft (20m)

Deoxidized copper pipe

Outer dia. : 3/8 in. (9.52mm)

Thickness : 1/32 in. (0.8mm)

NOTE :

Gas leak check position

Refrigerant flow (Cooling)

Refrigerant flow (Heating)

INDOOR UNIT

T1

TO

Temp. measurement

Indoor heat

exchanger

Cross flow fan

Deoxidized copper pipe

Outer dia. : 1/4 in. (6.35mm)

Thickness : 1/32 in. (0.8mm)

Sectional shape

of heat insulator

Allo

w

ab

le height

dif

ference :

33ft (

10m

)

Allo

w

ab

le pipe length

P

Pressure measurement
Gauge attaching port

Vacuum pump connecting port

Strainer

Pulse Modulating

valve at liquid side

Ø1.2 x 80

Ø1.2 x 80

TD

4-way valve

Compressor

DA111A1F-20F1

TS

T2

Outdoor heat

exchanger

Split capillary

Temp. measurement

Propeller fan Refrigerant amount : 2.43 lbs (1.10kg)

OUTDOOR UNIT

Muffler

Muffler

TE

TC

TA

charging of refrigerant, 0.22 oz/ft (20g/m) for the part of pipe exceeded 15m is required. [Max. 0.22 lbs (100g)]

Min. : 6.6ft (2m)

Chargeless : 50 ft (15m)

Charge : 0.22oz/ft

(51 to 66 ft)

[20g/m (16 to 20m)]

FILE NO. SVM-10019