Check procedure – Toshiba RAS-09LKV-UL User Manual

Page 78

Advertising
background image

– 78 –

(3) Only the indoor motor fan does not operate

<Primary check>
1. Is it possible to detect the power supply voltage (AC208–230V) between and on the terminal block?

2. Does the indoor fan motor operate in cooling operation?

(In heating operation, the indoor fan motor does not operate for approximately 10 minutes after it is turned

on, to prevent a cold air from blowing in.)

( RAS-09LKV-UL)

<Check procedure>

Replace the fan motor.

YES

NO

NO

YES

YES

NO

NO

YES

YES

NO

NO

YES

Does the fan stop in

no operating status?

Control P.C. board is defective.

Start the operation

with low fan setting

in cool operation.

Does AC 115 V

or higher voltage apply

to between red and black

lead of fan motor?

Does the fan rotate?

Change the setting of

cooling to high fan.

Operation

stops

Shut off the power supply.

Does the cross flow

fan rotate normally?

Is the rotation signal (DC+5 V 0 V)

output between

k

(gray lead wire)

and

l

(brown lead wire) of the motor

connector (CN33) when rotating the

cross flow fan by hand in no operating

status? (1 pulse/one turn)

Turn on the power supply.

Replace

bearing of cross

flow fan

Turn the power supply.

Shut off the

power supply once.

Does the fan speed

become higher?

Reconecting the

interconnetion cable

and terminal

block.

Replace the P.C. board.

Normal

Replace the control

P.C. board.

Does an operation

LED 1 Hz blink?

Check connecting

cable or power

supply cord complely?

Check 5V at

display unit?

Main P.C. Board?

Does the fan motor

operate smoothly?

YES

NO

YES

YES

Change Display unit

YES

Check 5V at

NO

NO

YES

FILE NO. SVM-10019

NO

NO

L1

L2