Toshiba RAS-09LKV-UL User Manual

Page 68

Advertising
background image

– 68 –

11-1. First Confirmation

11-1-1. Confirmation of Power Supply

Confirm that the power breaker operates (ON) normally.

11-1-2. Confirmation of Power Voltage

Confirm that power voltage is AC 208

230 ± 10%.

If power voltage is not in this range, the unit may not operate normally.

11-1-3. Operation Which is not a Trouble (Program Operation)

For controlling the air conditioner, the program operations are built in the microcomputer as described in the

following table.
If a claim is made for running operation, check whether or not it meets to the contents in the following table.
When it does, we inform you that it is not trouble of equipment, but it is indispensable for controlling and main-

taining of air conditioner.

Table 11-1-1

No.

1

2

3

4

5

6

Operation of air conditioner

When power breaker is turned “ON”, the

operation indicator (Green) of the indoor

unit flashes.

Compressor may not operate even if the

room temperature is within range of

compressor-ON.

In Dry and ECO mode, FAN (air flow)

display does not change even though FAN

(air flow select) button is operated.

Increasing of compressor motor speed

stops approx. 30 seconds after operation

started, and then compressor motor speed

increases again approx. 30 seconds after.

In AUTO mode, the operation mode is

changed.

In HEAT mode, the compressor motor

speed does not increase up to the maxi-

mum speed or decreases before the

temperature arrives at the set temperature.

Description

The OPERATION lamp of the indoor unit flashes when

power source is turned on. If [ ] button is

operated once, flashing stops.

(Flashes also in power failure)

The compressor does not operate while compressor

restart delay timer (3-minutes timer) operates.

The same phenomenon is found after power source has

been turned on because 3-minutes timer operates.

The air flow indication is fixed to [AUTO].

For smooth operation of the compressor, the compres-

sor motor speed is restricted to Max. 41 rps for 2 min-

utes, and Max.91 rps for 2 minutes to 3 minutes, respec-

tively after the operation has started.

After selecting Cool or Heat mode, select an operation

mode again if the compressor keeps stop status for 15

minutes.

The compressor motor speed may decrease by high-

temp. release control (Release protective operation by

temp.-up of the indoor heat exchanger) or current

release control.

FILE NO. SVM-10019