Battery Charging Reference

975-0170-01-01

B–5

Two-Stage Charging

If the two-stage charge is enabled, the charger finishes the absorption
charge but does not go to float mode because some battery manufacturers
advise against floating their batteries. The RS3000 goes into a monitoring
mode instead where the charger monitors the batteries but does not float
them.

A new two-stage charge cycle will be initiated under the same conditions
as for three-stage charging.

Charge Algorithm Graph

Charge Algorithm Definitions

Table B-1 Battery Defaults

Figure B-1 Three-Stage Charging Profile

Voltage

Flooded (or wet)

Gel

AGM

V

A

Absorption Voltage (VDC)

14.4

14.4

14.3

V

G

Gassing Voltage (VDC)

13.5

13.8

13.45

V

F1

Float Voltage (VDC)

13.5

13.8

13.45

V

F2

Float Exit Voltage (VDC)

12.5

12.5

12.5

I

H

I

B

V

F2

V

F1

V

G

V

A

Float

Time

T

CV

T

A

T

F

Bulk

Absorption