Lo DC Volt

Full name

Low DC input voltage shutdown

Configurable setting

This setting lets you set the low voltage shutdown level for the inverter.

You can adjust the Lo DC Volt settings as follows:

When to use

This setting limits the depth of discharge on your battery.

Batt Type

This feature is the same as described on the basic menu on page 3–16.

Batt Size

This feature is the same as described on the basic menu on page 3–17.

Sense Below

Configurable setting

This setting lets you adjust the load power at which the inverter will turn
on. This setting saves battery consumption by keeping the inverter
disabled (turned off) except when load demand is present.

You can adjust the Sense Below settings as follows:

When to use

Adjust this setting to control the inverter based on the load.

Outcome

Sets the load threshold at a power level where you want the inverter to
stay on, for example, when a sufficient load is applied. For more
information on this feature, see “Load Sense Mode” on page 2–6.

Lo DC Volt

[10.0V]

Range

Increment

Default

10 to 12 volts

0.1 volt

10 volts

Sense Below

[50W]

Range of values

Increment

Default

40 watts to 150 watts 10 watts

50 watts