Eqz Volts

Full name

Equalization voltage

Configurable setting

This setting lets you set the desired equalization voltage. This menu is
displayed only if charger equalization is enabled

.

Select a setting based on

the battery manufacturer’s recommendation. For more information, see
“Battery Charging Reference” on page B–1.

You can adjust Eqz Volts settings as follows:

Force Charge

Configurable setting

This setting forces the charger to be enabled (On) whenever you have
requalified AC. The default setting for Force Charge is On (enabled).

When to use

Turn Force Charge to On if you want to automatically start charging
whenever you connect to a qualified AC input, regardless of whether the
Charger is Enabled or Disabled.

Turn Force Charge to Off if you want charging to be determined only by
whether the Charger is Enabled or Disabled.

Outcome

If Force Charge is turned to On, the charger starts whenever you have
qualified AC.

Eqz Volts

[15.5V]

Range of values

Increment

Default

13.5 to 15.5 VDC

0.1 volts

15.5 VDC

Force Charge

[On]