Lo ac freq, Hi ac volt, Lo ac freq –25 hi ac volt –25 – Xantrex Technology RS3000 User Manual

Page 75

Advertising
background image

Configuration

975-0170-01-01

3–25

Lo AC Freq

Full name

Low AC transfer frequency (AC under frequency level)

Configurable setting

This setting lets you adjust the lowest frequency at which the
inverter/charger no longer qualifies AC as “good” and attempts to transfer
to invert mode.

You can adjust Lo AC Freq settings as follows:

When to use

This setting can be used when the AC supply frequency is lower than the
set value required for the electrical equipment.

Outcome

The lower frequency of the AC supply above which it will be qualified as
“good” by the inverter/charger can be varied.

Hi AC Volt

Full name

High AC transfer voltage (AC over voltage level)

Configurable setting

This setting lets you adjust the voltage above which the inverter/charger
no longer qualifies AC as “good” and transfers to Invert.

You can adjust Hi AC Volt settings as follows:

When to use

This setting lets you adjust the AC parameters when AC supply is outside
the upper voltage range required for electrical equipment.

Outcome

The upper limit of the voltage that will be qualified as “good” by the
inverter/charger can be varied.

Lo AC Freq

[55Hz]

Range of values

Increment

Default

55 to 58 Hz

1 Hz

55 Hz

Hi AC Volt

[135V]

Range of values

Increment

Default

120 to 145 VAC

1 volt

135 VAC