Sense interval, Cfg ac limits (configure ac limits), Chg stages – Xantrex Technology RS3000 User Manual

Page 72

Advertising
background image

Configuration

3–22

975-0170-01-01

Sense Interval

Configurable setting

This setting lets you adjust the interval between load sense pulses. The
longer the interval, the more power you will save. However, the longer
intervals may cause delays in the inverter powering up and starting your
loads. For more information on this feature, see “Load Sense Mode” on
page 2–6.

You can adjust Sense Interval settings as follows:

Cfg AC Limits (Configure AC Limits)

Cfg AC Limits is a sub-menu. If selected, a list of sub-menu items appear.
For more information on this sub menu, Configure AC Limits, see
page 3–24.

# Chg Stages

Full name

Number of charge stages

Configurable setting

These settings let you adjust your charger stages to either two-stage
charging or three-stage charging. The default setting for # Chg Stages is
3Stage. (See

“Battery Charging Reference” on page B–1

for an

explanation of two-stage and three-stage charging.)

Sense Interval

[1s]

Range of values

Increment

Default

1 to 25 seconds

1 second

1 second

# Chg Stages

[3Stage]