Xantrex Technology RS3000 User Manual

Page 89

Advertising
background image

Troubleshooting

975-0170-01-01

4–9

W9

Battery temp sensor
not detected. Check
connections.

Automatic

Battery Temperature
Sensor Not Present

Install a battery temperature
sensor (BTS). This warning
will continue to display as long
as no BTS is connected.

W10

Battery temp sensor
failure.

Automatic

Battery Temperature
Sensor Shorted

Replace battery temperature
sensor.

W11

Batt voltage too high.
Check DC wiring to
inverter/charger.

Automatic

DC Over Voltage
Warning

Turn off or check additional
charging sources to batteries.
Check battery cables.

W12

Battery voltage is
getting low.
Recharge battery.

Automatic

DC Under Voltage
Warning

Recharge batteries and check
battery cables from inverter to
batteries for loose connections.

W13

Line 1 AC voltage
too high. System may
shut down

Automatic

AC Over Voltage
Warning (AC Line 1
input)

Check AC input voltage.
Check high AC input voltage
setting.

W14

Line 1 AC voltage
too low. System may
shut down.

Automatic

AC Under Voltage
Warning (AC Line 1
input)

Check AC input voltage.
Check low AC input voltage
setting.

W15

Line 2 AC voltage
too high. System may
shut down.

Automatic

AC Over Voltage
Warning (AC Line 2
input)

Not applicable to RS3000.

W16

Line 2 AC voltage
too low. System may
shut down.

Automatic

AC Under Voltage
Warning (AC Line 2
input)

Not applicable to RS3000.

W18

Cannot Equalize

Manual

Cannot equalize

Wrong battery type. Change
battery type only if the battery
type setting is not the same as
actual battery type. Cannot
equalize a gel or AGM battery.

W19

Equalization
terminated
abnormally

Manual

Equalization
terminated abnormally

Investigate cause of problem.

W500

Lost network
connection

Automatic

Lost network
connection

Check network cables or
terminators.

Table 4-3 Warning Messages

Warning
Number Message

Warning
Type

Cause

Solution