Troubleshooting

4–12

975-0170-01-01

Table 4-4 provides a detailed description of the fault messages and
solutions. If you are unable to resolve the problem after referring to this
table, contact your dealer or Customer Service.

Table 4-4 Fault Messages

Fault
Number Message

Fault
Type

Cause

Solution

F0

is too hot and has
shut down. See
guide.

Automatic FET1

Over

Temperature Shutdown

Clear the fault and attempt
restart. Ensure adequate
ventilation around the RS3000.
Reduce AC loads.

F2

is too hot and has
shut down. See
guide.

Automatic

FET2 Over
Temperature Shutdown

Clear the fault and attempt
restart. Ensure adequate
ventilation around the RS3000.
Reduce AC loads.

F3

is too hot and has
shut down. See
guide.

Automatic Transformer

Over

Temperature Shutdown

Clear the fault and attempt
restart. Ensure adequate
ventilation around the RS3000.
Reduce AC loads.

F4

Battery over-temp.
Inv/Chg has shut
down. See guide.

Automatic

Battery Over
Temperature Shutdown

Clear the fault and attempt
restart. Stop charging, check
battery voltage and
temperature. Check for
excessive ambient temperature
and adequate ventilation in the
battery compartment.

F5

is too hot and has
shut down. See
guide.

Automatic Ambient

Over

Temperature Shutdown

Clear the fault and attempt
restart. Ensure adequate
ventilation around RS3000.
Reduce AC loads.

F6

Too many AC loads.
Turn some off, clear
fault, try again.

Escalating
Auto Fault.
Must occur
3 times in
30 seconds
before
becoming
a manual
fault.

AC Overload
Shutdown (AC
OUTPUT)

Clear the fault and attempt
restart. Reduce AC loads.