Control panel calibration, Initial display setup – Grain Systems Bucket Elevtors, Conveyors, Series II Sweeps PNEG-720-G2 User Manual

Page 56

Advertising
background image

5. Assembly

56

PNEG-720-G2 12" and 16" Series II Sweep

Control Panel Calibration

Observe the tractor drive motor nameplate and the auger drive motor nameplate.

Record the full load amp (FLA) value for the specific voltage on each motor.

Auger drive motor full load amps: ____
Tractor drive motor full load amps: ____

Switch the disconnect switch on the panel to OFF (not ON).

Unlock and open the control panel.

Adjust the FLA dial screw on the tractor drive motor contactor (M1) and the auger drive motor
contactor (M2) so that the indicator arrowhead is set slightly higher than the full load amp value listed
on the nameplates.

Tractor drive motor contactor (M1) FLA adjustment dial: ____
Auger drive motor (M2) FLA adjustment dial value: ____

Close and lock the control panel.

Switch the disconnect switch on the panel to ON (not OFF).

Initial Display Setup

NOTE: If no keys are activated for 2 minutes, the display returns to the default state without saving any

configuration changes. At each value, after 5 seconds of inactivity, a description of the current
state will scroll across the display.

NOTE: Pressing and hold OK will return to the previous menu or return to the default state without saving

the changed values or parameters.

Press OK on the display unit.

(IN) should be displayed on the unit.

Press

or

on the display unit until (CURR) is shown (not VOLT, POTM or TEMP).

Press OK.

(RANG) should be displayed on the unit.

Press

or

on the display unit until 4-20 is shown (not 0-20).

Press OK.

(DEC.P) should be displayed on the unit.

Press

or

on the display unit until 11.11 is shown (not 1111, 111.1, 1.111 or .1111).

Press OK.

(DI.LO) should be displayed on the unit.

Press

or

on the display unit until 0 is shown.

Press OK.

Advertising