Chapter 4

Absolute Reset and

Absolute Battery

199

4.2.1

Absolute encoder backup specifications

Item

Specifications

Battery model

AB-7

Quantity

1 pc/axis (8 units max. / 8 axes)

Battery voltage

3.6V

Current capacity

3300mAH

Reference for battery replacing timing

(Note 1)

Approx. 3 years

(It varies significantly by the effects of the

usage condition)

(Note 1) Replace the battery regularly.

4.2.2

Absolute Battery Charge

Please have the battery charged for more than 72 hours before using for the first time or after

replacing with a new one. The battery gets charged while the controller is supplied with 24V

power.

Data holding time

Upper limit of encoder revolution at

power-off [rpm]

Parameter

No.19 setting

When the connected

actuator is a model

other than RCA2-***N;

When the connected

actuator is RCA2-***N;

Reference for

battery retaining

time [days]

Holding time per

hour of battery

charge time

(reference) [H]

0

100

75

20

6.6

1

200

150

15

5.0

2

400

300

10

3.3

3

800

600

5

1.6

(Note 1) Followings are the reference values of time assuming the battery is new.

Leaving the controller power OFF for more than the data holding time will lead to a loss of the

data. Have the battery charged as early as possible.

There is life to the battery and the duration for data holding will decrease. Replace the battery

with a new one if the retaining time is remarkably dropped even with enough charging time.

(Example) From Monday to Friday : charge for 8 hours per day, discharge for 16 hours,

Saturday and Sunday : When using with discharge

Connected axis : Any model except for RCA2-***N

Storage for 120 [H] if fully charged

1) If parameter No.19 = 3 setting;

Total charge amount : Operation hours per day 8 [H] × Retaining time per charge for 1

hour 1.6 [H] × Weekday 5 [days] = 64 [H]

Total discharge amount : Stopped time during night 16 [H] x Weekday 5 [days] + Stopped

time on Saturday and Sunday 48 [H] = 128 [H]

Total discharge amount : 16 [h] × 5 [day] + 48 [h] = 128 [h]

ĺ If starting on Monday with a full-charge, the total amount of the discharge in a week

exceeds total amount of battery charge in 64 [H], thus the fully charged storage

decreases by 64 [H]. Therefore, it is necessary to have the battery fully charged in

every 10-day period.

2) If parameter No.19 = 2 setting;

Total charge amount : Operation hours per day 8 [H] × Retaining time per charge for 1

hour 3.3 [H] × Weekday 5 [days] = 132 [H]

Total discharge amount : Stopped time during night 16 [H] x Weekday 5 [days] + Stopped

time on Saturday and Sunday 48 [H] = 128 [H]

ĺ If starting on Monday, because the total amount of charge has exceeded the total

amount of discharge, it is not necessary to have a continuous full charge. 4-hour

charge is stored every week. Please note, however, the upper limit is 120 [H].