29-5

2 Digital I/O Units

29

Expansion Modules

Writing to an external output

■

Output refresh
Outputs are refreshed every 10 ms independent of the screen scan.
HG Digital Output (LEY) are reflected in the digital I/O unit.

■

Output delay
The min-to-max delay time for HG Digital Output (LEY) to fire from the digital I/O unit is 1 ms to 11 ms. This does not
affect the display processing

Control processing

Digital I/O unit output

Output

refresh

LEY

LEY

Y

10 ms

Output

refresh

10 ms

Output

refresh

10 ms

Scan time

Output

delay

Output

delay

Start of scan

Display

processing

1 scan

External output

Y

External output

HG Digital

Output

HG Digital

Output

End of scan

The maximum output delay is 11 ms, which is the operating time of
the output refresh.

LEY

Y

Output

refresh

Output delay

(maximum)

HG Digital

Output

External output