5 saving and deleting data, Saving data, Saving and deleting data -7 – IDEC High Performance Series User Manual
Page 805: Alarm log function

WindO/I-NV2 User’s Manual
13-7
1 Overview
13
Alarm Log Function
1.5 Saving and Deleting Data
●
Saving Data
You can select whether or not to save the sampled data in the data storage area. The method to save data is
configured on the Channel tab in the Alarm Log Settings dialog box.
When Saving Data to the Data Storage Area
Select Store under Data in the Auto-Setup dialog box or in the Individual Settings dialog box.
If the number of active alarms exceeds the Alarm Log data storage amount set for the data storage area, the data is
processed with either of the following methods.
■
Fixed
If the saved data exceeds the Alarm Log data storage amount, the new data is not saved.
■
Rotate
If the saved data exceeds the Alarm Log data storage amount, the oldest data is deleted and the new data is saved.
MICRO/I
Host
0
1
12:00
0
1
12:53
12:00
Alarm occurred
12:53 Recovered
12:54 Confirmed
Alarm Log data
No.
Message
Occurrence Time
Recovery Time
ConfirmaƟon Time
1-1
Voltage drop
12/01/2011 12:00:00
12/01 12:53:10
12/01 12:54:30
Alarm Log data storage amount
New data
Alarm Log data storage amount
Oldest data
(delete)
New data
When the backup battery is depleted and for the HG2G-5ST22VF-*, the data in the Alarm Log is erased
when the MICRO/I is turned off.