1 Overview

13-6

WindO/I-NV2 User’s Manual

For sampled data, the format for displayed items varies based on the output method.

■

Batch
Batch output shows the recovery and confirmation time for an alarm that has occurred on a single line.
The labels displayed in the label row are “Ch.No.”, “Message”, “Occurrence Time”, “Recovery Time”, and “Confirmation
Time”.
Example: When the message for channel number 1-1 is “Voltage drop” and the message for channel number 1-2 is

“Temperature abnormal”

■

Real Time
Real time output displays the alarm state and the time the alarm became that state on a single line each time an
alarm occurs, is recovered from, or is confirmed.
The labels displayed in the label row are “Ch.No.”, “Message”, “State”, and “Time”.
Example: When the message for channel number 1-1 is “Voltage drop” and the message for channel number 1-2 is

“Temperature abnormal”

Ch.No.

Message

Occurrence Time

Recovery Time

Confirmation Time

1-1

Voltage drop

12/01/2011 12:50:00

12/01 12:50:20

12/01 12:50:30

1-2

Temperature abnormal

12/01/2011 12:50:10

--

12/01 12:52:10

1-1

Voltage drop

12/01/2011 12:51:00

--

--

Ch.No.

Message

State

Time

1-1

Voltage drop

Occurred

12/01/2011 12:50:00

1-2

Temperature abnormal

Occurred

12/01/2011 12:50:10

1-1

Voltage drop

Recovered

12/01/2011 12:50:20