TRM-203 AND TRM-403 USER’S MANUAL

REV 1

26

For this example, press the

[1]

key for a Delta type transformer.

e. The following menu will be displayed:

Select the test current by pressing the corresponding numeric key on the keypad. Press
the

[6]

key (CUSTOM) if you would like to enter a custom test current and then enter

the current (between 1A-40A) on the next screen.

f. The following screen will be displayed:

1. YES

Press the

[1]

key (YES) if you wish to convert readings to standard temperature. The

following screen will be displayed:

Press the

[1]

key (COPPER, Tk=234.5) to select copper as the winding material.

Continue to step g.

Press the

[2]

key (ALUMINUM, Tk=225.0) to select aluminum as the winding

material. Continue to step g.

Press the

[3]

key (MANUALLY ENTER Tk) to manually enter the Tk value. The

following screen will be displayed:

WINDING MATERIAL:

1.

COPPER, TK=234.5

2.

ALUMINUM, TK=225.0

3.

MANUALLY ENTER TK



CONVERT READINGS TO

STANDARD TEMP?

1.

YES

2.

NO



SELECT TEST CURRENT:
1.

1A

2.

5A

3.

10A

4.

20A

5.

40A

6.

CUSTOM