TRM-203 AND TRM-403 USER’S MANUAL

REV 1

44

h. The following screen will be displayed:

Select the phase to test by pressing the corresponding numeric key. For this example,
we will be testing phase H/X1-H/X0, so press the

[1]

key.

i. The following screen will be displayed:

Select the test current by pressing the corresponding numeric key on the keypad. Press
the

[6]

key (CUSTOM) if you would like to enter a custom test current and then enter

the current (between 1A-40A) on the next screen.

j. The following screen will be displayed:

1. YES

Press the

[1]

key (YES) if you wish to convert readings to standard temperature. The

following screen will be displayed:

CONVERT READINGS TO

STANDARD TEMP?

1.

YES

2.

NO



SELECT TEST CURRENT:
1.

1A

2.

5A

3.

10A

4.

20A

5.

40A

6.

CUSTOM

SELECT PHASE:
1.

H/X1-H/X0 (YN PH A)

2.

H/X2-H/X0 (YN PH B)

3.

H/X3-H/X0 (YN PH C)

4.

H/X1-H/X3 (Δ PH A)

5.

H/X2-H/X1 (Δ PH B)

6.

H/X3-H/X2 (Δ PH C)