h. The following screen will be displayed:
Select the phase to test by pressing the corresponding numeric key. For this example,
we will be testing phase H/X1-H/X0, so press the
[1]
key.
i. The following screen will be displayed:
Select the test current by pressing the corresponding numeric key on the keypad. Press
the
[6]
key (CUSTOM) if you would like to enter a custom test current and then enter
the current (between 1A-40A) on the next screen.
j. The following screen will be displayed:
1. YES
Press the
[1]
key (YES) if you wish to convert readings to standard temperature. The
following screen will be displayed:
CONVERT READINGS TO
STANDARD TEMP?
1.
YES
2.
NO
SELECT TEST CURRENT:
1.
1A
2.
5A
3.
10A
4.
20A
5.
40A
6.
CUSTOM
SELECT PHASE:
1.
H/X1-H/X0 (YN PH A)
2.
H/X2-H/X0 (YN PH B)
3.
H/X3-H/X0 (YN PH C)
4.
H/X1-H/X3 (Δ PH A)
5.
H/X2-H/X1 (Δ PH B)
6.
H/X3-H/X2 (Δ PH C)