REV 1 TRM-203 AND TRM-403 USER’S MANUAL

47

After the TRM finishes its internal calibration, the following screen will be displayed:

p. The TRM determines when the resistance reading is stable and displays the resistance

values on the LCD screen as shown below:

Press the

[ENTER]

key to accept and save the readings for this tap.

q. The following screen will be displayed momentarily:

Once the reading has been saved, the following screen will be displayed:

Set the LTC or Voltage Regulator tap position to the position indicated on the LCD screen
and press the

[START]

key.

The TRM will continue the test and display the results as in step n. Repeat steps p
through q
for all “Lower” positions and then through all “Raise” positions.


set tap to 2 lower

"START" to CONTINUE


** XFMR ENERGIZED! **

*XFMR CHARGING*


I = 39.91 AMPS

R = 1.491

m

Ω

===

>

TEST SAVED!

<

===

** XFMR ENERGIZED! **

TEST IN PROGRESS 7

I = 39.91 AMPS

R = 1.491

m

Ω

"ENTER" TO ACCEPT TAP
** XFMR ENERGIZED! **

*XFMR CHARGING*

H/X1-H/X0

please wait...

I = 39.98 AMPS

** XFMR ENERGIZED! **