TRM-203 AND TRM-403 USER’S MANUAL

REV 1

46

Press the

[ENTER]

key to confirm the D.U.T. temperature setting.

l. The following screen will be displayed:

Use the

[]

and

[]

keys to adjust the reference temperature.

Press the

[ENTER]

key to confirm the reference temperature setting.

m. The following screen will be displayed:

n. The following screen will be displayed:

Set the LTC or Voltage Regulator tap position to the position indicated on the screen. To
change tap positions, press and hold the

[RAISE]

or

[LOWER]

LTC control button on

the front panel. Release the button when the tap position has been set to the position
indicated on the screen. Press the

[START]

key.

o. The following screen will be displayed momentarily:

calibrating

please wait...





STATIC LTC H/X1-H/X0

40 AMP TEST

set tap to 3 lower

"START" to RUN TEST

OR

"STOP" TO ABORT

***** WARNING! *****

DANGEROUS FLASH-OVER
WILL OCCUR IF CABLES
ARE DISCONNECTED!
********************

REFERENCE TEMP:

75.0

°

C 167.0

°

F


↑↓

to adjust tk

"ENTER" to accept