REV 1 TRM-203 AND TRM-403 USER’S MANUAL

43

d. The following screen will be displayed

Type the number of taps the LTC or Voltage Regulator has using the alpha-numeric
keypad, and then press the

[ENTER]

key. We will enter “3” for our example.

e. The following screen will be displayed:

Select the number of neutral taps by pressing the corresponding numeric key on the
keypad.

f. The following screen will be displayed:

If the tap information is correct, press the

[1]

key (YES) and continue to step f.

If the tap information is incorrect, press the

[2]

key (NO) and return to step d.

g. The following screen will be displayed:

For this example, we will test a single phase, so press the

[4]

key (SINGLE PHASE).

1.

DELTA

2.

WYE (WITH NEUTRAL)

3.

WYE (NO NEUTRAL)

4.

SINGLE PHASE



3 LOWER, -N-, 3 RAISE

IS THIS CORRECT?
1.YES
2.NO

NUMBER OF NEUT TAPS:
1.ONE
2.THREE
3.FIVE


ENTER NUMBER OF RAISE
TAPS, NOT COUNTING
NEUTRALS (1-16):