Vanguard TRM-203_403 User Manual
Page 42
TRM-203 AND TRM-403 USER’S MANUAL
REV 1
38
i. The following screen will be displayed:
This warning is a reminder that the next sequence of test steps will run current through
the test load.
Press any key to continue.
j. The following screen will be displayed:
Press the
[START]
key to run the test.
k. The following screen will be displayed momentarily:
After the TRM finishes its internal calibration, the following screen will be displayed:
This is an informational screen to remind the operator that a test is in progress and
shows which phase the test is being performed on. The display duration of this message
depends on the size of the winding’s inductance.
*XFMR CHARGING*
H/X1-H/X0
please wait...
** XFMR ENERGIZED! **
calibrating
please wait...
SING PHS H/X1-H/X0
40 amp test
"start" to run test
or
"stop" to abort
***** WARNING! *****
DANGEROUS FLASH-OVER
WILL OCCUR IF CABLES
ARE DISCONNECTED!
********************