Vanguard TRM-203_403 User Manual
Page 57
REV 1 TRM-203 AND TRM-403 USER’S MANUAL
53
1. YES
Press the
[1]
key (YES) if you wish to convert readings to standard temperature. The
following screen will be displayed:
Press the
[1]
key (COPPER, Tk=234.5) to select copper as the winding material.
Continue to step h.
Press the
[2]
key (ALUMINUM, Tk=225) to select aluminum as the winding material.
Continue to step h.
Press the
[3]
key (MANUALLY ENTER Tk) to manually enter the Tk value. The
following screen will be displayed:
You can increase the Tk value by 0.5
°C increments by pressing the
[∧]
key.
You can decrease the Tk value by 0.5
°C increments by pressing the
[∨]
key.
Press the
[ENTER]
key to confirm the temperature setting. Continue to step h.
2. NO
Press the
[2]
key (NO) if you do NOT wish to convert readings to standard
temperature. Continue to step j.
TK:
230.0
°
C
↑↓
to adjust tk
"ENTER" to accept
WINDING MATERIAL:
1.
COPPER, TK=234.5
2.
ALUMINUM, TK=225.0
3.
MANUALLY ENTER TK