IM 12A00A01-61E

3-24 Foundation Fieldbus

The SIMULATE parameter of AI block consists of the elements listed in Table 3.23 below.

Table 3.23 SIMULATE Parameter

Sub-index

Parameters

Description

1

Simulate Status

Sets the data status to be simulated.

2

Simulate Value

Sets the value of the data to be simulated.

3

Transducer Status

Displays the data status from the transducer block. It cannot be changed.

4

Transducer Value

Displays the data value from the transducer block. It cannot be changed.

5

Simulate En/Disable

Controls the simulation function of this block.
1: Simulation disabled (standard)
2: Simulation started

When Simulate En/Disable in Table 3.23 above is set to 2, the applicable function block uses the simula-
tion value set in this parameter instead of the data from the transducer block. This setting can be used for
propagation of the status to the trailing blocks, generation of a process alarm, and as an operation test for
trailing blocks.