IM 12A00A01-61E

Foundation Fieldbus 3-31

3-31

Relative

Parameter

Factory

Write

Index

Name

Default

Mode

Explanation

22

ALARM_SUM

The current alert status, unacknowledged states, unreported states, and

disabled states of the alarms associated with the function block.

23

ACK_OPTION

0xFFFF

AUTO

Selection of whether alarms associated with the block will be automatically

acknowledged.

24

ALARM_HYS

0.5%

AUTO

Amount the PV must return within the alarm limits before the alarm condition

clears. Alarm Hysteresis is expressed as a percent of the PV span.

25

HI_HI_PRI

0

AUTO

Priority of the high high alarm.

26

HI_HI_LIM

+INF

AUTO

The setting for high high alarm in engineering units.

27

HI_PRI

0

AUTO

Priority of the high alarm.

28

HI_LIM

+INF

AUTO

The setting for high alarm in engineering units.

29

LO_PRI

0

AUTO

Priority of the low alarm.

30

LO_LIM

-INF

AUTO

The setting for the low alarm in engineering units.

31

LO_LO_PRI

0

AUTO

Priority of the low low alarm.

32

LO_LO_LIM

-INF

AUTO

The setting of the low low alarm in engineering units.

33

HI_HI_ALM

The status for high high alarm and its associated time stamp.

34

HI_ALM

The status for high alarm and its associated time stamp.

35

LO_ALM

The status of the low alarm and its associated time stamp.

36

LO_LO_ALM

The status of the low low alarm and its associated time stamp.