6 list of parameters for each block of the exa, 6-1 resource block, 6 list of parameters for each block of the exa -28 – Yokogawa DO202 2-Wire Dissolved Oxygen Analyzer User Manual

Page 33: 6-1 resource block -28

Advertising
background image

IM 12A00A01-61E

3-28 Foundation Fieldbus

3-6� List of parameters for each block of the EXA
Note: The Write Mode column contains the modes in which each parameter is write enabled.
O/S: Write enabled in O/S mode.
MAN: Write enabled in Man mode and O/S mode.
AUTO: Write enabled in Auto mode, Man mode, and O/S mode.

3-6�-1 Resource Block

Relative

Index

Index

Parameter

Name

Factory Default

Write

Mode

Explanation

0

1000 Block Header

TAG:“RS”

Block Tag
= O/S

Information on this block such as Block Tag, DD Revision,
Execution Time etc.

1

1001 ST_REV

The revision level of the static data associated with the resource
block. The revision value is incremented each time a static
parameter alue in this block is changed.

2

1002 TAG_DESC

Null

AUTO

The user description of the intended application of the block.

3

1003 STRATEGY

1

AUTO

The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.

4

1004 ALERT_KEY

1

AUTO

The identification number of the plant unit. This information may
be used in the host for sorting alarms, etc.

5

1005 MODE_BLK

AUTO

AUTO

The actual, target, permitted, and normal modes of the block.

6

1006 BLOCK_ERR

This parameter reflects the error status associated with the
hardware or software components associated with a block. It is a
bit string, so that multiple errors may be shown.

7

1007

RS_STATE

State of the resource block state machine.

8

1008 TEST_RW

AUTO

Read/write test parameter-used only for conformance testing and
simulation.

9

1009 DD_

RESOURCE

Null

String identifying the tag of the resource which contains the
Device Description for this resource.

10

1010 MANUFAC_ID

0x00594543

Manufacturer identification number-used by an interface device
to locate the DD file for the resource.

11

1011 DEV_TYPE

PH202: 0x0830
SC202: 0x0831
ISC202: 0x0832
DO202: 0x0833

Manufacturer’s model number associated with the resource-used
by interface devices to locate the DD file for the resource.

12

1012 DEV_REV

3

Manufacturer revision number associated with the resource-used
by an interface device to locate the DD file for the resource.

13

1013 DD_REV

1

Revision of the DD associated with the resource-used by an
interface device to locate the DD file for the resource.

14

1014 GRANT_DENY

0

AUTO

Options for controlling access of host computer and local control
panels to operating, tuning and alarm parameters of the block.

15

1015 HARD_TYPES

Scalar input

The types of hardware available as channel numbers.
bit0: Scalar input
bit1: Scalar output

bit1: Scalar output

bit2: Discrete input

bit2: Discrete input

bit3: Discrete output

bit3: Discrete output

16

1016

RESTART

Allows a manual restart to be initiated. Several degrees of restart
are possible. They are 1: Run, 2: Restart resource, 3: Restart
with initial value specified in FF functional spec. (*1), and 4:
Restart processor.
*1: FF-891 Foundation TM Specification Function Block

*1: FF-891 Foundation TM Specification Function Block

Application Process Part 2.

17

1017 FEATURES

Soft write lock
supported
Report supported

Used to show supported resource block options.

18

1018 FEATURE_SEL

Soft write lock
supported
Report supported

AUTO

Used to select resource block options defined in FEATURES.
bit0: Scheduled
bit1: Event driven
bit2: Manufacturer specified

19

1019 CYCLE_TYPE

Scheduled

Identifies the block execution methods available for this resource.

20

1020 CYCLE_SEL

Scheduled

AUTO

Used to select the block execution method for this resource.

21

1021

MIN_CYCLE_T

3200 (100ms)

Time duration of the shortest cycle interval of which the resource
is capable.

22

1022

MEMORY_SIZE 0

Available configuration memory in the empty resource. To be
checked before attempting a download.

23

1023

NV_CYCLE_T

0

Interval between writing copies of NV parameters to non-volatile
memory. Zero means never.

24

1024

FREE_SPACE

0

Percent of memory available for further configuration. EXA has
zero which means a preconfigured resource.

Advertising