3-4. Wiring the contact signals

3-4-1. General precautions

The contact output signals consist of volt-

age-free relay contacts for switching electrical

appliances (SPDT). They can also be used as

digital outputs to signal processing equipment

(such as a controller or PLC). It is possible to

use multi-core cables for the contact in and

output signals and shielded multi-core cable for

the analog signals.

3-4-2. Contact outputs

The EXAxt 450 unit’s four contacts (switches)

that can be wired and configured to suit user

requirements. Contact S4 is programmed as

a fail-safe contact. Please refer to section 5-8,

Contact output setup for functionality descrip-

tion.

Alarm (limits monitoring)

Contacts configured as “ALARM” can be ener-

gized when limits are crossed.

Fail

Contacts configured as “FAIL” will be energized

when a fail situation occurs. Some fail situa-

tions are automatically signaled by the internal

diagnostics (electronics) of the converter.

Others can be configured by the user (see

section 5-11 Error Configuration). By pressing

the “INFO” button on the main screen the user

is given an explanation as well as a remedy for

the current fail situation.

Always connect the fail contact to an alarm

device such as a warning light, alarm bell or

displayed on an annunciator.

“ALARM” Contact “FAIL” Contact

Power Off

NC

NC

Power On

NC

NC

Alarm

NO

NC

Fail

NC

NO

Fail and Alarm

NC*

NO

HOLD**

NC

NC

* When a fail situation occurs which is related

to the parameter associated with the contact

(pH, ORP, rH or temperature) the contact

will go to NC. When the fail situation is not

related to the parameter associated with the

contact the contact will remain in the state it

is currently in.

** Wash cycles do not influence other contacts.

When HOLD is enabled during wash, it is

HOLD that will set all contacts to NC.

3-4-3. Contact input

It is necessary to use screening/shielding on

the input signal cables. Terminal 63 is used to

connect the shielding.

3-5. Wiring the mA-output signals

3-5-1. General precautions

The analog output signals of the EXAxt

transmit low power standard industry signals to

peripherals like control systems or strip-chart

recorders (Figure 3-6).

3-5-2. Analog output signals

The output signals consist of active current

signals of 4-20 mA. The maximum load can be

600 ohms on each.

It is necessary to use screening/shielding on

the output signal cables. Terminal 63 is used to

connect the shielding.

Figure 3-8-a. External grounding

Figure 3-8-b. Internal grounding

2

N

1

L

POWER

100-240 VAC/15 VA/ 50/60Hz

FUSE: 500 mA/250 VAC/T

AC

(M4 screw)

(M4 screw)