5-13. Advanced setup

Defaults

The functionality of the EXAxt allows to save

and load defaults to come to a known instru-

ment setting. The EXAxt has both factory and

user defined defaults.

After a “load default” the instrument will reset.

The following parameters are not included in

the defaults

1. X-axis timing

2. Auto return (10 min / disabled)

3. Tag

4. Passwords

5. Date and time

6. Language

7. The contents of all logbooks

8. HART parameters

(address, tag, descriptor, message)

Tag

A tag provides a symbolic reference to the

instrument and is defined to be unique

throughout the control system at one plant site.

A tag can contain up to 12 characters. If the

instrument is purchased with the /SCT option,

the TAG is pre-programmed with the specified

tagnumber.

Passwords

Calibration and Commissioning may be sepa-

rately protected by a password. By default both

passwords are empty. Entering an empty pass-

word results in disabling the password check.

A password can contain up to 8 characters.

When a password is entered for the calibration

and commissioning a 4-digit operator ID can be

entered. One can also leave the ID empty.

Date/time

The Logbooks and trend graph use the clock/

calendar as reference. The current date and

time is set here. The current time is displayed

in the third “zoom” menu.

Note! The fixed format is YYYY/MM/DD HH:

MM:SS

HART

The address of the EXAxt in a HART network

can be set. Valid addresses are 0...15.

FACTORY ADJUSTMENT

This menu is for service engineers only.

This section is protected by a password.

Attempting to change data in the factory adjust-

ment menu without the proper instructions

and equipment, can result in corruption of the

instrument setup, and will impair the perform-

ance of the unit.