WW

Sets the Web homepage

Syntax

WW p1,p2,p3,p4<terminator>
p1

Homepage type

OPERATOR

Operator page

MONITOR

Monitor page

p2

Homepage ON/OFF

p3

Authentication

OFF

No authentication

ADMIN

Administrator privileges

USER

User privileges

p4

Command input (USE, NOT)

Query

WW[ p1]?

Example

Enable the operator page, disable the
authentication, and enable command input.
WWOPERATOR,ON,OFF,USE

Description • Parameter p3 and p4 are valid when p2 is ON.

• Parameter p4 is valid when p1 is set to

OPERATOR.

YQ

Sets the application timeout

To not use the timeout feature

Syntax

YQ p1<terminator>
p1

Application timeout (OFF)

Query

YQ?

Example

Disable timeout.
YQOFF

Description The settings specified with this command take

effect when you save the settings with the XE
command and power-cycle the MV.

To use the timeout feature

Syntax

YQ p1,p2<terminator>
p1

Application timeout (ON)

p2

Timeout value [minutes] (1 to 120)

Query

YQ?

Example

Enable the application timeout and set the
timeout value to 3 min.
YQON,3

Description The settings specified with this command take

effect when you save the settings with the XE
command and power-cycle the MV.

YT

Sets the FTP transfer timing

Syntax

YT p1,p2,p3<terminator>
p1

Auto transfer when display and event data

files are generated (ON/OFF)

p2

Auto transfer when report data files are

generated (ON/OFF)

p3

Auto transfer when snapshot data files are

generated (when snapshot is executed) (ON/
OFF)

Query

YT?

Example

Auto transfer display and event data files. Do not
transfer report data files. Do not transfer image
data files.
YTON,OFF,OFF

Description If the method to save data to an external storage

medium is set to Auto, the MV automatically
transfers data files as they are generated. For
media storage settings, see the RD-MV1000/RD-
MV2000 User’s Manual
.

YU

Sets the contents to be sent via

e-mail

To send changes in the alarm status

Syntax YU p1,p2,p3,p4,p5,p6,p7,p8,p9,p10,

p11,p12<terminator>

p1

Transmitted content (ALARM)

p2

Recipient 1 ON/OFF

p3

Recipient 2 ON/OFF

p4

Alarm transmission of alarm number 1 ON/OFF

p5

Alarm transmission of alarm number 2 ON/OFF

p6

Alarm transmission of alarm number 3 ON/OFF

p7

Alarm transmission of alarm number 4 ON/OFF

p8

Include instantaneous data ON/OFF

p9

Include source URL ON/OFF

p10

Subject (up to 32 alphanumeric characters)

p11

Header 1 (up to 64 characters)

p12

Header 2 (up to 64 characters)

Query

YU[ p1]?

Example

Transmit alarms of alarm numbers 1 to 4
including instantaneous data but not including
the source URL to recipient 1. Set the subject to
“ALM” and header 1 to “LP2.”
YUALARM,ON,OFF,ON,ON,ON,ON,ON,OFF,AL
M,LP2

To send e-mail at scheduled times

Syntax

YU p1,p2,p3,p4,p5,p6,p7,p8,p9,p10,
p11,p12<terminator>
p1

Transmitted content (TIME)

p2

Recipient 1 ON/OFF

p3

Interval for sending e-mail to recipient 1

(1H, 2H, 3H, 4H, 6H, 8H, 12H, 24H)

p4

Time when e-mail is sent to recipient 1 (00:00

to 23:59)

p5

Recipient 2 ON/OFF

p6

Interval for sending e-mail to recipient 2

(1H, 2H, 3H, 4H, 6H, 8H, 12H, 24H)

p7

Time when e-mail is sent to recipient 2 (00:00

to 23:59)

p8

Include instantaneous data ON/OFF

p9

Include source URL ON/OFF

p10

Subject (up to 32 alphanumeric characters)

p11

Header 1 (up to 64 characters)

p12

Header 2 (up to 64 characters)

Query

YU[ p1]?

Example

Send e-mail at 17 hours 15 minutes every day
to recipient 1. Do not include instantaneous data
but include the source URL. Set the subject to
“GOOD” and header 1 to “LP2.”
YUTIME,ON,24H,17:15,OFF,,,OFF,ON,
GOOD,LP2